MH300 Series Technical Datasheet |
Basic Function |
Max Frequency | V/F control: 0-3200Hz, vector control:1:300Hz |
Carrier Frequency | 0.5Khz-16Khz, automatically adjust per load characteristics |
Input Frequency Resolution | digital setting: 0.01Hz; analog setting: Max frequency x0.025% |
Control Mode | VFD, SVC, FVC |
Starting Torque | 0Hz/180%(FVC), 0.5Hz/150%(SVC), 0.5Hz/100%(V/F) |
Speed Range | 1:1000(FVC), 1:200(SVC), 1:50(V/F) |
Steady Speed Precision | ±0.02%(FVC) |
Torque Control Precision | ±5%(FVC) |
Overload | 150% rate current 60s; 180% rated current 3s. |
Torque Increase | Automati torque enhancement; Manual torque improvement0.1%-30.0% |
V/F Curve | three way: linear; multipoint; N-power V/F curve(1.2-power, 1.4-power, 1.6-power, 1.8-power, 2-power) |
V/F Separate | 2 way: full separation, semi-detached |
Acceleration Deceleration Curve | linear or S-curve plus deceleration. Four acceleration and the range deceleration times 0.0-6500.0s |
DC Brake | DC brake frequency: 0.00Hz-Max frequency Brake time: 0.0s-36.0s Braking action current value:0.0%-100.0% |
Inching Control | Inching frequency range: 0.00Hz-Max frequency Inching deceleration time: 0.0s-6500.0s |
Simple PLC, Multistage Running | Through built-in PLC or control terminal to realize Max 16 speed running |
Bulti-in PID | To realize the process control closed-loop control system |
Automatic Voltage Regulation(AVR) | When the grid voltage changes, to keep output constant voltage |
Overpressure Loss Rate Control | Automatic limit of current voltage during operation to prevent overcurrent overvoltage to stop |
Fast Current Limiting Funication | Maximum reduce overcurrent failure to protect the frequency converter normal run |
Torque Limitation and Control | Feature of excavator, automatic limiation of torque during operation to prevent frequency overcurrent to stop; Closed-loop vector mode can realize torque control. |
Personalization Feature |
Outstanding Performance | With high performance current vector control technical to realize and control asynchronous and synchronous motor |
Instantaneous Stop Constantly | In the instantaneous power fail, through load to feedback energy to make up the voltage reduce, to maintance frequency converter to keep running in a short time |
Rapid Current Limiting | To avoid frequency converter frequent appear overcurrent fault. |
Virtual I/O | Five groups of virtual DIDO to realize simple logic control |
Timing Control | Timing control funication: setting range time 0.0Min-6500.0Min |
Multimotor Switching | Four group motor parameters, can realize four motor to switch control. |
Motor Overheat Protection | Select IO expansion card 1, analog input A13 can accept motor temperature sensor input(PI100, PI1000) |
Running |
Input Terminal | Standard: 5 digital input terminals One of them support Max 100Khz high speed pluse input, 2 pcs analog input terminal, 1 only support 0-10V voltage input, 1 support 0-10V voltage input or 4-20mA current input Extension Ability: 5 digital input terminal 1 analog input terminal, support -10V∼10V voltage input, and support PI100/PI1000 |
Output Terminal | Standard: 1 high speed pluse output terminals(can optional to be open collector type), support 0-100Khz square wave signal output 1 digital output terminal 1 relay output terminal 1 analog output terminal, support 0-20mA current output or 0-10V voltage output Extension Ability: 1 digital output terminal 1 relay output terminal 1 analog output terminal, support 0-20mA current output or 0-10V voltage output |
Command Source | Operation panel given, control terminal, serial port given. It can switch by my ways. |
Frequency Source | 10 frequency source: digital given, analog current given, pluse given, serial port given. It can switch by many ways. |
Auxiliary Frequency Source | 10 kinds auxiliary frequency source. Flexible to realize auxiliary frequency fine turning, frequency synthesls. |
Display and Keyboard |
LED display | Display parameters |
LCD display | Optional part, chinese or english operation content |
Keyboard locking and funication selection | Realize part of key or all to lock, or define the scope part of key, to prevent the wrong operation |
Protection Function | Power on motor short circcuit detection, input output loss phase protection, overcurrent protection, overvoltage protection, under-voltage protection, overheat protection, overload protection, etc., |
Environment |
Using place | Indoor, not exposed to direct sunlight, dust, corrosive gas, flammable gas, oil, fog, water vapor, water or salt |
Altitude | |
Environment Temperature | -10℃~+40℃(environment temperature in 40℃~50℃, please derating use |
Humidity | <95% RH, no water condense |
Vibration | <5.9m/s²(0.6g) |
Store Humidity | -20℃~+60℃ |